Mounting & Installation
Technical Data
Typical Schematic
Electrical Data
Supply: 100 - 230VAC -/+ 10%, 50/60 Hz
Terminals max wire size: 1 x 2.5mm
2
or 2 x 1.5mm
2
per circuit
iCANnet™ inputs/output: Screw terminals
iCANnet™ output current: 300mA Max @ nominal 15V
DALI output screw terminals: Max wire size 2.5mm
2
DALI signal: Nominal 16V, max current 250mA supplies to each universe.
Guaranteed minimum current: 240mA.
Automatic shut-down and restart after short-circuit (maximum 1 per bus) according to IEC 62386-101
Protection: Provided by installer
Mechanical Data
Weight: 0.35 kg
Operating temperature: +2ºC to +50ºC
Max storage temperature: +60ºC
Humidity: +5 to 95% non-condensing
Environmental protection: IP20
Installation: Installation must be carried out by a suitably qualified electrician and installed in a suitable DINrail
enclosure rated for the intended environment.
SCMD2
2 Universe Addressable
DALI-2 Controller
Document Number: 9850-000771-04
SCMD2 must be mounted in a suitable enclosure to provide regulatory
protection from electric shock hazard as well as protecting the iCANnet
data network from tampering that could lead to reduced network security.
Ensure selected enclosure provides adequate cooling ventilation.
Fixing to DIN rail
1. Fix top clips over DIN rail.
2. Pull down bottom clip using screwdriver.
3. Close module towards DIN rail.
4. Push up bottom clip to fix securely to DIN rail.
Removing from DIN rail
1. Pull down bottom clip with screwdriver.
2. Lift module away from DIN rail.
1
2
3
4
1
2
Control Plate
Control Plate
iCANnet
DALI Line
SCMD2
DALI
Control Plate
DALI
Sensor
DALI
Drivers / Ballasts
Network Sensor
E&OE. iLight reserve the right to make
changes to the equipment without
prior notice.
© Signify Holding
iLight
Usk House, Lakeside
Llantarnam Park,
Cwmbran,
NP44 3HD, UK
t: +44 (0)1923 495495
www.iLight.co.uk
EU Authorised Representative
Cooper Lighting Netherlands B.V.
High Tech Campus
HTC 48
Eindhoven
5656 AE
Installation Guide
Dimensions