GAS CONVERSION KIT FOR FIREPLACES WITH ELECTRONIC IGNITION

PROPANE TO NATURAL GAS (ECOFLOW VALVE)

[FOR USE IN FIREPLACE MODELS LISTED IN TABLE 1 ON PAGE 2]

DR

AF

T

09

/12

/20

17

KIT COMPONENTS

 

Main Burner Orifice, Low-Rate Orifice, Conversion Sticker and

 

Conversion Sticker Form (to be filled out and affixed by installer)

REQUIRED TOOLS AND SUPPLIES

 

Safety Gloves, Adjustable Wrench, Channel Locks, Flat Blade  

 

Screwdriver, 4mm Allen Wrench (for some pilot assemblies - see 

 

Figure 7), 5/16” Nutdriver, Pipe Joint Compound or Teflon Tape

TURN OFF THE GAS SUPPLY TO THE APPLIANCE. DISCONNECT 

ELECTRICAL POWER SUPPLY. 
READ ALL THE STEPS BEFORE STARTING THE CONVERSION. IN-

STALLER NOTICE: THESE INSTRUCTIONS MUST BE LEFT WITH THE 

APPLIANCE.
When installing gas components use pipe joint compound or 

Teflon tape on all pipe fittings before installing (Do not use pipe 

joint compounds on flare fittings).
NOTE: THE FIREPLACE MUST BE OFF AND COLD BEFORE PERFORM-

ING THE GAS CONVERSION.
ALL WARNINGS, PRECAUTIONS AND INSTRUCTIONS IN THE INSTAL-

LATION AND OPERATION MANUAL PROVIDED WITH THE APPLIANCE 

APPLY TO THESE INSTRUCTIONS.

GENERAL INFORMATION

Gas conversion kits are available to adapt the fireplace from the 

use of one type of gas to the use of another. These kits contain all 

the necessary components needed to complete the task including 

labeling that must be affixed to ensure safe operation.

       

WARNING

This conversion kit shall be installed by a qualified 

service agency in accordance with the manufac-

turer's instructions and all applicable codes and 

requirements of the authority having jurisdiction.  If 

the information in these instructions is not followed 

exactly, a fire, explosion or production of carbon 

monoxide may result causing property damage, 

personal injury or loss of life.  The qualified service 

agency performing this installation is responsible 

for the proper installation of this kit and assumes 

responsibility for this conversion. The installation 

is not proper and complete until the operation of the 

converted appliance is checked as specified in the 

manufacturers instructions supplied with the kit. 

 IMPORTANT LE CANADA SEULEMENT

La conversion devra être effectuée conformément aux 

recommandations des autorités provinciales ayant 

juridiction et conformément aux exigences du code 

d'installation CAN/CSA B149.1.

         IMPORTANT CANADA

The conversion shall be carried out in accordance with 

the requirements of the provincial authorities having 

jurisdiction and in accordance with the requirements 

of the CAN/CSA B149.1 Installation code.

            

AVERTISSEMENT

Cet équipement de conversion sera installé par 

une agence qualifiée de service conformément aux 

instructions du fabricant et toutes exigences et codes 

applicables de l'autorisés avoir la juridiction.  Si 

l'information dans cette instruction n'est pas suivie 

exactement, un feu, explosion ou production de 

protoxyde de carbone peut résulter le dommages 

causer de propriété, perte ou blessure personnelle de 

vie.  L'agence qualifiée de service est esponsable de 

l'installation propre de cet équipment.  L'installation 

n'est pas propre et compléte jusqu'à l'opération de 

l'appareil converti est chéque suivant les critères 

établis dans les instructions de propriétaire provi-

sionnées avec l'équipement.

ECOFLOW GAS CONVERSION KITS

P/N 900751-00
Rev. B, 09/2017

HEARTH PRODUCTS

KITS AND ACCESSORIES

IHP.us.com

900751-00B

1

f i r e - p a r t s . c o m

Summary of Contents for GCK-SKT385131PN

Page 1: ...the information in these instructions is not followed exactly a fire explosion or production of carbon monoxide may result causing property damage personal injury or loss of life The qualified service agency performing this installation is responsible for the proper installation of this kit and assumes responsibility for this conversion The installation is not proper and complete until the operati...

Page 2: ...st convert the unit to adjust for varying altitudes a deration information sticker must be filled out by the installer and adhered totheapplianceatthetimeoftheconversion Contact your local gas supplier for deration requirements for your area 1 TURN OFF THE GAS SUPPLY TO THE FIREPLACE Disconnect power supply at the circuit breaker Ensure fireplace is cold 2 Remove the barrier facade and glass door ...

Page 3: ... The front and rear burner orifices are different sizes Refer to Table 5 on Page 6 for verification of proper front and rear burner orifice sizes supplied in kit Figure 6 Pilot Hood Figure 5A Figure 5B Stem Plug Natural Gas Positioning Step 5A Change the Stem Position on the Plug See Figures 5A and 5B Step 5B Figure 5B shows the stem plug positioning for Natural Gas Step 6 Pull the pilot hood stra...

Page 4: ...rning characteristics of the ap pliance WARNING Never use an open flame to check for leaks BURNER AIR SHUTTER ADJUSTMENT INSTRUCTIONS 1 Adjust the air shutters per instructions in Figures 8A and 8B and Table 2 2 Light the fireplace Follow the lighting procedure on the lighting label in the control compartment 3 Allow the burner to operate for at least fifteen 15 minutes while observing the flame c...

Page 5: ...ent See Table 2 for the standard adjustment setting Closed Open Rear Air Shutter Adjustment Lever Step 15 Relight the main burner The lighting instructions can be found on the lighting label in the control compartment Verify proper burner ignition and operation Figure 9 Inspect the pilot system for proper flame The pilot flame should engulf the flame sensor Figure 11 Using a manometer test the inl...

Page 6: ...oved for clarity 1 8 Inlet gas pressure test point plug in control compartment Testing Inlet Gas Pressure Qualified Technicians Only 1 Turn off gas shutoff valve and electrical 2 Remove 1 8 plug shown in diagram below 3 Install an 1 8 nipple in place of plug 4 Connect manometer to nipple using an 1 8 NPT air hose nipple fitting 5 Turn on shutoff valve and check for proper inlet gas pressure 6 Reve...