71
TROUBLESHOOTING
• Incorrect handling of the thermostat, safety valve, or other valves may lead to tank rupture. When servicing the unit
follow the instructions carefully:
• Always turn off the main power supply when the water supply is being shut off.
• Test the free operation of the safety valve regularly by opening the valve ensuring the water flows freely.
• Electrical connection and all servicing of the electrical components should only be carried out by an authorized
electrician.
• Fitting and all servicing of plumbing fixtures should only be carried out by an authorized installer.
• When replacing the thermostat, safety valve, or any other valve or part supplied with this unit, use only approved
parts of the same specification.
ERROR CODES
If the unit has some problems and does not work normally, an error code is shown on the OUTDOOR UNIT main PBA or
LCD of the wired remote controller.
DISPLAY
EXPLANATION
ERROR
SOURCE
101
Hydro Unit / Outdoor Unit communication connection error
Hydro Unit
120
Short- or open-circuit error of the room temperature sensor of Zone 2
indoor unit (detected only when the room thermostat is used)
Hydro Unit
121
Short- or open-circuit error of the room temperature sensor of Zone 1
indoor unit (detected only when the room thermostat is used)
Hydro Unit
122
EVA Inlet temp sensor SHORT or OPEN
Hydro Unit
123
EVA Outlet temp sensor SHORT or OPEN
Hydro Unit
162
EEPROM Error
Hydro Unit
198
The error of the Terminal Block's Thermal Fuse (Open)
Hydro Unit
201
Hydro Unit / Outdoor Unit communication error (Matching error)
Hydro
Unit/Outdoor
Unit
202
Hydro Unit / Outdoor Unit communication error (3 min)
Hydro
Unit/Outdoor
Unit
203
Communication error between INVERTER and MAIN MICOM (4 min)
Outdoor Unit
221
Outdoor Unit air temperature sensor error
Outdoor Unit
231
Condenser temperature sensor error
Outdoor Unit
251
Discharge temperature sensor error
Outdoor Unit
320
OLP sensor error
Outdoor Unit
403
Detection of freezing (During cooling operation)
Outdoor Unit
404
Protection of Outdoor Unit when it is overloaded (during Safety Start, Normal
operation state)
Outdoor Unit
407
Comp down due to high pressure
Outdoor Unit
416
Discharge of a compressor is overheated
Outdoor Unit
419
OUTDOOR UNIT EEV operation error
Outdoor Unit
425
Power source line missing error (only for 3-phase model)
Outdoor Unit
440
Heating operation blocked (outdoor temperature over 35 °C)
Outdoor Unit
441
Cooling operation blocked (outdoor temperature under 9 °C)
Outdoor Unit
458
OUTDOOR UNIT fan1 error
Outdoor Unit
461
[Inverter] Compressor startup error
Outdoor Unit
462
[Inverter] Total current error/PFC over current error
Outdoor Unit
463
OLP is overheated
Outdoor Unit
464
[Inverter] IPM over current error
Outdoor Unit
465
Compressor overload error
Outdoor Unit
466
DC LINK over/low voltage error
Outdoor Unit
467
[Inverter] Compressor rotation error
Outdoor Unit
468
[Inverter] Current sensor error
Outdoor Unit
Summary of Contents for Inuit 6I
Page 1: ...5 INSTALLATION MANUAL AIR TO WATER HEAT PUMP IGLU INUIT...
Page 16: ...16 IGLU Inuit 6WTI indoor unit...
Page 17: ...17 IGLU Inuit 9I outdoor unit IGLU Inuit 9I indoor unit...
Page 18: ...18 IGLU Inuit 9WTI outdoor unit IGLU Inuit 9WTI indoor unit...
Page 19: ...19 IGLU Inuit 12I IGLU Inuit 16I outdoor unit IGLU Inuit 12I IGLU Inuit indoor unit...
Page 27: ...27 SPACE REQUIREMENTS FOR OUTDOOR UNIT WHEN INSTALLING ONE OUTDOOR UNIT...
Page 43: ...43...