48
HOW TO CONNECT YOUR EXTENDED POWER CABLES
Prepare your tools.
Tools
Specification
Shape
Crimping pliers
MH-14
Connection sleeve (mm)
20x6.5 (HxOD)
Insulation tape
Width 19mm
Contraction tube (mm)
70x8 (LxOD)
As shown in the figure, peel off the shields from the rubber and wire of the power cable.
Peel off 20 mm of cable shields from the pre-installed tube.
For information about the power cable specifications for indoor and outdoor units, refer to the installation
manual.
After peeling off cable wires from the pre-installed tube, insert a contraction tube.
If cable wires are connected without using connecting sleeves, their contact area becomes reduced, or
corrosion develops on the outer surfaces of the wires (copper wires) over a long time. This may cause an
increase in resistance (reduction of passing current) and consequently may result in a fire.
Insert both sides of the core wire of the power cable into the connection sleeve.
Method 1: Push the core wire into the sleeve from both sides.
Method 2: Twist the wire cores together and push it into the sleeve.