44
CONNECTING THE CABLES
I
GLU® Inuit 6I/ IGLU® Inuit 6WTI
RATED
VOLTAGE RANGE
MCA
MFA
HZ
Volt
Min
Max
Min. Circuit
amps.
Max. Circuit
amps.
50
220-240
198
264
16.0A
20.0A
I
GLU® Inuit 9I/ IGLU® Inuit 9WTI
RATED
VOLTAGE RANGE
MCA
MFA
HZ
Volt
Min
Max
Min. Circuit
amps.
Max. Circuit
amps.
50
380-415
342
457
10.0A
16.1A
I
GLU® Inuit 12I/ IGLU® Inuit 12WTI
RATED
VOLTAGE RANGE
MCA
MFA
HZ
Volt
Min
Max
Min. Circuit
amps.
Max. Circuit
amps.
50
380-415
342
457
10.0A
16.1A
I
GLU® Inuit 16I/ IGLU® Inuit 16WTI
RATED
VOLTAGE RANGE
MCA
MFA
HZ
Volt
Min
Max
Min. Circuit
amps.
Max. Circuit
amps.
50
380-415
342
457
12.0A
16.1A
The power cable is not supplied with Air to Water Heat pump.
Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F)
This Equipment complies with IEC 61000-3-12.
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to
3.3[MVA] at the interface point between the user's supply and the public system. It is the responsibility of the installer or
the user of the equipment to ensure, by consultation with a distribution network operator, if necessary, that the equipment
is connected only to a supply with a short-circuit power Ssc greater than or equal to 3.3[MVA].
SPECIFICATION OF CONNECTION CABLES (COMMON IN USE)
I
GLU® Inuit 6I/ IGLU® Inuit 6WTI
POWER SUPPLY
MAX/MIN (V)
COMMUNICATION CABLE
1F, 220-240 Vac, 50 Hz
±10%
0.75
̴1.5 mm
2,
, 2 Wires
I
GLU® Inuit 9I/ IGLU® Inuit 9WTI
POWER SUPPLY
MAX/MIN (V)
COMMUNICATION CABLE
3F, 380-415 Vac, 50 Hz
±10%
0.75
̴1.5 mm
2,
, 2 Wires
I
GLU® Inuit 12I/ IGLU® Inuit 12WTI
POWER SUPPLY
MAX/MIN (V)
COMMUNICATION CABLE
3F, 380-415 Vac, 50 Hz
±10%
0.75
̴1.5 mm
2,
, 2 Wires
I
GLU® Inuit 16I/ IGLU® Inuit 16WTI
POWER SUPPLY
MAX/MIN (V)
COMMUNICATION CABLE
3F, 380-415 Vac, 50 Hz
±10%
0.75
̴1.5 mm
2,
, 2 Wires
For Power Cable, use the grade H07RN-F or H05RN-F materials.
Power supply cords of parts of appliances for outdoor use shall
not be lighter than polychloroprene sheathed flexible cord. (Code
designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245
IEC 66 / CENELEC: H07RN-F)
When installing the outdoor unit in a computer room or network
room, server room, or in the presence of risk of disturbance to the
communication cable, use the double shielded (tape aluminum /
polyester braid + copper) cable of FROHH2R type.
Summary of Contents for Inuit 6I
Page 1: ...5 INSTALLATION MANUAL AIR TO WATER HEAT PUMP IGLU INUIT...
Page 16: ...16 IGLU Inuit 6WTI indoor unit...
Page 17: ...17 IGLU Inuit 9I outdoor unit IGLU Inuit 9I indoor unit...
Page 18: ...18 IGLU Inuit 9WTI outdoor unit IGLU Inuit 9WTI indoor unit...
Page 19: ...19 IGLU Inuit 12I IGLU Inuit 16I outdoor unit IGLU Inuit 12I IGLU Inuit indoor unit...
Page 27: ...27 SPACE REQUIREMENTS FOR OUTDOOR UNIT WHEN INSTALLING ONE OUTDOOR UNIT...
Page 43: ...43...