TOCSIN 750 Sampler End of Line Filter Assembly

Deployment

Tocsin 750 Series Addressable Sample Modules are designed to sample using 6mm OD x 

4mm ID tubing from locations up to 20M distant from the module. IGD provide  EOL (End 

Of Line) filter modules to prevent dirt and debris from being drawn into the system. 

Part Number TOC-750S-FIL

There are two methods to deploy the EOL assembly. Under ideal circumstances the 

assembly should be fitted as indicated in fig 1 at the very end of the sample tube. This 

provides best protection.

In some circumstances this option may not be possible, for example access to the filter 

may be limited or the nature of the environment may prohibit. In this case the filter can be 

fitted at a convenient position in the tube run as close to the end of the sample line as 

possible to protect as much of the tubing as possible. This is indicated in fig 2

Note that the stainless steel housing is designed to be mounted to a suitable surface. The 

cover then provides mechanical protection for the filter whilst still being able to view its 

condition. Note correct orientation of the filter.

Fig 1. Filter Installed End of Sample Line
Picture Shows Cover Fitted

Fig 2. Filter Installed ‘into’ The Sample Line
Run. Note Picture Shown Cover
Removed.

Note Correct
Orientation of 
Filter. In this 
orientation dirt 
collects on the 
outside of the 
filter and will be 
visible through 
the cover window

Direction

of

Flow

Replacement Filter 
Part Number 
TOC-750S-PCF

Summary of Contents for TOC-750S-CO

Page 1: ...Addressable 2 Wire Document Ref SL 065 v1 2 Operation Manual Sampler Module FS646773 EMS696504 Triton House Crosby Street Stockport SK2 6SH internationalgasdetectors com 44 0 161 483 1415 sales intern...

Page 2: ...e TOC 750S CO TOC 750S CO2 TOC 750S FIL TOC 750S H2 TOC 750S IRF TOC 750S N20 TOC 750S NH3 TOC 750S O2 TOC 750S PN1 TOC 750S TBE TOC 750S PN2 TOC 750S CBF TOC 750S SLF TOC 750S PCF TOC 750S INF Descri...

Page 3: ...t Active Zero Filter Physical Details Sample and exhaust ports suit 6mm OD x 4mm ID Soft tubing IGD Part Number TOC 750S TBE supplied as 20M coils Samplers are designed for ambient sampling only Only...

Page 4: ...minated and cables are stripped to the enclosed guide See Cable Calculator for Cable Core Size vs Distance VS Number of Devices Cable Screen or Drain Wire Tubing 6 x 4 Polyurethane Other Tube Options...

Page 5: ...e limited or the nature of the environment may prohibit In this case the lter can be tted at a convenient position in the tube run as close to the end of the sample line as possible to protect as much...

Page 6: ...ise for suitable lters to match the environmental condition Optional Protection Filter Note these are advised to suit the application consult IGD for further details Where termination is required thro...

Page 7: ...rs to remove any traces of the target gas from the zero air stream For example Ammonia LPG Fit activated Carbon Filter PN TOC 750S CBF CO2 t Soda Lime Filter Part Number TOC 750S SLF For Oxygen detect...

Page 8: ...ptions are active and which of those options are communicating see previous section on Module Indications 00 08 16 24 01 09 17 25 02 10 18 26 03 11 19 27 04 12 20 28 05 13 21 29 06 14 22 30 07 15 23 3...

Page 9: ...ion using IGD s interface cable as indicated below Apps can be downloaded from the App store Interface Cable PN TOC CBL SET NOTE When undertaking work with a connected tablet ensure the system control...

Page 10: ...cked For example with new internal and EOL lters tted the running pressure is 990mBar With lters removed the running pressure is 1002 mBar So the lters and sample line impose a 12mBar pressure drop Th...

Page 11: ...he sample pump purge time expires Note 1 Most detectors can be set to auto zero Ensure either an appropriate scrubber is tted to the zero port or the zero port is tubed away to a clean air location Do...

Page 12: ...ring the zero or calibration process With this arrangement set the ow rate from the gas cylinder such that the owmeter shows 0 5L Min of gas ow spilling o This arrangement allows the sampler to take i...

Page 13: ...o zero the detector Now apply calibration gas as indicated The graph should show the signal rise as the detector responds to gas and gives a visual indication to show when the reading has stabilised O...

Reviews: