Alarm Change Over relay (volt free)
Relay is normally ON, De-energising
on alarm condition.

NC

COM

NO

Power Supply: 

Environmental:    

Response Time:

Nominal Alarm Levels:

Expected Life:

Target Gas:

Standards Applied:

Cabling:

Service:

12 to 28V DC   4W

0 to +55 Degrees Centigrade
0-95%RH Non-condensing
Terminal Enclosure IP54 Cable Glands Must be used

<30 Seconds

See preset alarm levels Relay Active SPCO 5A @ 230V AC Non inductive

5 Years, no user replaceable parts

See cover markings as CO, CO2, O2, LPG, CH4

This equipment must only be serviced by competent persons and checked 
periodically using traceable calibration gases. Do not test using lighter fuel or 
similar fuel gases as this can give misleading results. In extreme cases this can
result in sensor damage. 

EN50194-1:2009   Type A Equipment  

When using stranded cable fit bootlace ferrules to
Prevent stray wire strands shorting

EN60335-1:2002   EN50270

Internal Terminal Functions

24V DC

0V DC

Installation of this device when connecting to a mains power supply should only be made by a competent 
person. The unit is supplied pre-calibrated. Clean only using a damp cloth, DO NOT USE CLEANING 
PRODUCTS.

Do not tamper with this equipment. To do so may cause incorrect operation or risk electric shock.

Connection for flammable gas detector

Connection for 
O2/Toxic/IR gas detector

Connection Point for LED Module

Digital Output
(Sounder)

Digital Input
(Push Button)

Supply
Out

Supply
IN

NOTE: The unit is shipped configured and Pre-Calibrated for its detector and options and alarm levels

Internal Relay Active on alarm

Note relay is normally energised and 
turns OFF on alarm.

Relay is mains rated to 5A and can be 
used to control other 3rd party devices

(Flammable Gas Detectors)

Main Base PCB Connectors

When unplugging detectors from the main PCB DO NOT lever them off. This will potentially cause damage to the 
PCB and/or connector mating parts and invalidate any warranty. If it is necessary to remove the PCB connectors use 
long nose pliers.

+55 C

-10 C

Locating the Detector

The TOC-750 Flammable gas detector is factory calibrated for its target gas. The target gas is indicated on the 
product (i.e CH4, LPG etc). The TOC-750 will respond to any flammable gas but can only be calibrated to be 
correct response to one. The following list indicates common materials that may also cause a response in 
operation:

Aerosol propellants (Butane)
Paint solvents (VOC’s)
Hot vaporised cooking oils
Solvent based adhesives (VOC’s)

Some commonly occurring substances may cause long term detector damage, typically:

Silicones (furniture polishes etc)
Hair sprays (silicones, VOC’s etc)
Chlorinated cleaning agents