9.1 Parameters
Parameter
Explanation
ou2
Configuration of the analogue signal: I = 4���20 mA or Ineg = 20���4 mA
or OFF = output off
P-n
Switching logic for the diagnostic output: PnP or nPn�
ASP2
Analogue start point for measured temperature value�
AEP2
Analogue end point for measured temperature value�
FOU2
Analogue signal in case of an alarm: On = 21�5 mA; OFF = 3�5 mA�
ccL
Calibration check limit = temperature deviation between the process
value and the reference value from which the unit provides a warning�
uni
Setting of the standard unit of measurement: °C or °F�
LED mode
The LED on the unit can be switched on and off:
On = LED always on
Off = LED always off
Notification = LED only on in case of a warning or an alarm�
Restore Factory
Settings
Restore the factory settings�
We recommend recording your own settings before carrying
out a reset
�
9.2 Analysis functions
Displays /
commands
Explanation
Free-text fields for
device information
-Application Specific Tag
-Function Tag
-Location Tag
-Installation date
Diagnostics display
-Hi = highest temperature value measured
-Lo = lowest temperature value measured
Flash On / Flash Off
The LED starts flashing, allowing easy identification of the unit
in the field�
Reset
-[Hi] and [Lo] memory
-[Hi] memory
-[Lo] memory
Reset the maximum and/or minimum value memories