FOU2 Response of the analogue signal when a diagnostic case is signalled:
> Instead of the measured temperature value a defined current value according
to Namur NE43 is provided (On: 21�5 mA; OFF: 3�5 mA)
dOU1
Response of the diagnostic switching output when a diagnostic case is signalled:
> Output opens / closes / pulsates depending on the category of the diagnostic
case�
Setting options see Table 4
P-n
Switching logic for the diagnostic switching output: pnp or npn�
HI
Read max� value of the temperature measured in the process�
LO
Read min� value of the temperature measured in the process�
Fnr
Read fault number
�
rES
Restoring the factory settings�
It is recommended to note down your own settings before carrying out a
reset
�
9 Operation
When the supply voltage is applied, the unit is in the RUN mode after a power-on
delay time of 8 s (= normal operating mode)� It carries out its measurement and
evaluation functions and provides output signals according to the set parameters�
10 Technical data
Technical data and scale drawing at www�ifm�com�
10.1 Setting range for drW / drA
Medium temperature
Setting range
-10���100 °C
14���212 °F
0�2���5 K
-25���0 °C
-13���32 °F
0�3���5 K
> 100 °C
> 212 °F
x...5 K (→ chart)