SmartPLC DataLine with EtherNet/IP device interface
84
>
Configure the IP parameters manually
41608
To configure the IP parameters of the configuration interface manually:
1 Select the menu page
►
>
►
Select [IP setup] tab.
2 Deactivate the NTP client
►
Uncheck [Obtain IP address autom.] (→
Notes on IP settings
(→ S.
>
The IP address fields [IP address], [Subnet mask] and [Gateway address] can be edited.
3 Configure the IP parameters
►
Configure the following parameters as required (→
Notes on IP settings
(→ S.
– [IP address]
– [Subnet mask]
– [Gateway address]
4 Save the changes
►
Press [Accept] button.
>
Selected values are applied.
>
[IP status] displays the active configuration method: [
Static]
>
Configure the IP parameters automatically
41604
The device must be connected to a DHCP server to automatically receive the interface
parameters via DHCP.
► Connect the configuration interface (X3) to a DHCP server.
To configure the IP parameters of the configuration interface automatically:
1 Select the menu page
►
>
►
Select [IP setup] tab.
2 Enable the NTP client
►
Activate the [Obtain IP address autom.] (→
Notes on IP settings
3 Save the changes
►
Press [Accept] button.
>
The device tries to obtain the IP parameters from a DHCP server.
>
If the configuration of IP parameters via DHCP server fails, the device will generate the IP parameters with the
Zeroconf protocol.
>
[IP address], [Subnet mask] and [Gateway address] display the set IP parameters.
>
Selected values are applied.
>
[IP status] displays the active configuration method:
DHCP
or
Zeroconf
.
The automatic configuration of the IP parameters takes approx. 10 seconds.
>