Operating instructions  

AS-i SmartLine module

AC3218 

AC3219 

80255917/00      01/2017

UK

Summary of Contents for SmartLine AC3218

Page 1: ...Operating instructions AS i SmartLine module AC3218 AC3219 80255917 00 01 2017 UK...

Page 2: ...on of an actuator with intrinsic supply 7 6 2 3 Connection of an actuator with separate 24 V supply 8 6 2 4 Electrical connection 0 V terminal 8 6 3 Connection analogue module AC3219 0 10 V 9 6 3 1 Co...

Page 3: ...or the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Functions and features If the operating instructions or the techni...

Page 4: ...3218 Rmin for voltage output 1 k AC3219 AS i profile S 7 3 6 Maximum number of modules per AS i system 31 Conversion time digital analogue in the slave with four channels 1 ms Actuator supply from AS...

Page 5: ...ace between the unit and the top and bottom of the control cabinet to enable air circulation and to avoid excessive heating Take into account the internal heating of all devices when mounting several...

Page 6: ...stallation of electrical equipment must be adhered to Disconnect power Connect the unit 6 1 Wiring O actuator supply 24 V C1 C4 analogue output current AC3218 V1 V4 analogue output voltage AC3219 O ac...

Page 7: ...and O are not used with actuators without separate voltage supply 1 Analogue module 2 Actuator without separate supply 6 2 2 Connection of an actuator with intrinsic supply O C1 C4 0 V O A 2 wire actu...

Page 8: ...not connect the 0 V terminals analogue output 0 V of the respective channels of the current output modules to each other This connection leads to faulty current signals The connection of the 0 V term...

Page 9: ...3 Connection analogue module AC3219 0 10 V 6 3 1 Connection of an actuator with intrinsic supply O V1 V4 0 V O An actuator with intrinsic supply e g a voltmeter is connected via the terminals V1 4 and...

Page 10: ...be taken from the terminals V1 V4 and 0 V The terminals O and 0 V must be con nected to each other via a link 1 Analogue module 2 Actuator with separate supply 7 Parameter setting Parameter bit Desig...

Page 11: ...711 2CEC on above nominal range 11 5 V 11500 2CEC flashing overflow 8 3 Transmission time of the analogue values The transmission time of the analogue values depends on the conversion time of the digi...

Page 12: ...eripheral fault is indicated if at least one of the analogue signals is outside the value range LED yellow DIAG DIAG lights DIAG flashes DIAG off Internal diagnostics no fault internal fault replace m...

Page 13: ...13 UK 11 Scale drawing 108 25 4 93 126 LED 35...