10.1.3 Timeout
If no button is pressed for 30 s during parameter setting, the unit returns to the
operating mode with unchanged values�
10.2 Scaling of the analogue value for temperature (OUT1)
►
Select [ASP1] and set the value at which 4 mA is provided�
►
Select [AEP1] and set the value at which 20 mA is provided�
10.3 Scaling of the analogue value for volumetric flow (OUT2)
►
Select [ASP2] and set the value at which 4 mA is provided�
►
Select [AEP2] and set the value at which 20 mA is provided�
10.4 User settings (optional)
10.4.1 Determine the standard unit of measurement for volumetric flow
►
Select [uni�F] and set the unit of measurement: Lmin, m3h, GPm or GPh�
10.4.2 Determine the standard unit of measurement for temperature
►
Select [uni�T] and set the unit of measurement: °C or °F�
10.4.3 Standard display
►
Select [SELd] and define the standard unit of measurement
FLOW = display shows the current volumetric flow value in the standard unit of
measurement�
TEMP = display shows the current medium temperature in the standard unit of
measurement�
►
Select [diS] and set the update rate and orientation of the display:
d1 = update of the measured values every 50 ms�
d2 = update of the measured values every 200 ms�
d3 = update of the measured values every 600 ms�
rd1, rd2, rd3 = display like d1, d2, d3; rotated by 180�
OFF = the display is switched off in the operating mode� The LEDs remain active
even if the display is deactivated� Error messages are displayed even if the display is
deactivated�
10.4.4 Measured value damping
► Select [dAP] and set the damping constant in seconds (τ value 63 %).