Air gap sensor
SDP110
25
10.2.2.1 Process value for OUTx
u
Select the OUTx menu.
u
Select [SELx] and set the process value for output x:
•
DIST: Distance
•
FLOW: Flow
•
PRES: Pressure
10.2.2.2 Standard unit of measurement
u
Select the CFG menu.
u
Select [uni.D] and set the unit of measurement for the distance: µm or none (without unit of
measurement).
u
Select [uni.F] and set the unit of measurement for the flow: l/min, m
3
/h, m/s, ft
3
/min, ft
3
/h, ft/s.
u
Select [uni.P] and set the unit of measurement for the pressure: kPa, bar, psi.
10.2.3 Setting the output functions
The parameters for distance monitoring, flow monitoring and pressure monitoring are set in the
same way. The prerequisite is that the process value for OUTx has first been defined via
[SELx].
10.2.3.1 Limit monitoring OUTx / hysteresis function
u
Select the OUTx menu.
u
Select [oux] and set the switching signal:
•
Hno: hysteresis function / normally open
•
Hnc: hysteresis function / normally closed
u
Select [SPx] and set the measured value at which the output switches.
u
Select [rPx] and set the measured value at which the output switches off.
10.2.3.2 Limit monitoring OUTx / window function
u
Select the OUTx menu.
u
Select [oux] and set the switching signal:
•
Fno: window function / normally open
•
Fnc: window function / normally closed
u
Select [FHx] and set the upper limit of the window section.
u
Select [FLx] and set the lower limit of the window section.
10.2.3.3 Analogue signal OUT2
u
Select the OUT2 menu.
u
Select [ou2] and set the function:
I: flow-proportional current signal 4…20 mA.
u
Select [ASP2] and set the measurement value at which the output signal is 4 mA.
u
Select [AEP2] and set the measurement value at which the output signal is 20 mA.