Flow meter compressed air
SDGx50
31
– OU: The output switches ON for pressure measurement and OFF for flow measurement and
temperature measurement.
•
Analogue signal:
– On: The analogue signal goes to 21.5 mA.
– OFF: The analogue signal goes to 3.5 mA.
– OU: The analogue signal goes to 21.5 mA for pressure measurement. The analogue signal
goes to 3.5 mA for flow measurement and temperature measurement.
The parameter FOUx is not available if [ou] = Imp (consumed quantity monitoring) is selected.
The pulses are provided independent of the fault.
11.5.11 Lock / unlock
The unit can be locked electronically to prevent unintentional settings. Factory setting: not locked.
Locking:
u
Make sure that the unit is in the normal operating mode.
u
Press [▲] and [▼] simultaneously for 10 s until [Set menu lock] is displayed.
Unlocking:
u
Make sure that the unit is in the normal operating mode.
u
Press [▲] and [▼] simultaneously for 10 s until [Reset menu lock] is displayed.
11.5.12 Factory reset
u
Select the EF menu.
u
Select [rES].
u
Briefly press [●].
u
Keep [▼] or [▲] pressed.
w
[----] is displayed.
u
Briefly press [●].
w
The unit carries out a reboot.
We recommend documenting your own settings in the chapter Factory setting before carrying
out a reset.
11.6 Diagnostic functions
11.6.1 Reading minimum values / maximum values
u
Select the MEM menu.
u
Select [Lo.x] or [Hi.x] to display the highest or lowest process value measured:
Lo.F: Minimum value of the flow value measured in the process (flow volume or flow velocity)
Hi.F: Maximum value of the flow value measured in the process (flow volume or flow velocity)
Lo.T: Minimum value of the temperature measured in the process
Hi.T: Maximum value of the temperature measured in the process
Lo.P: Minimum value of the pressure measured in the process
Hi.P: Maximum value of the pressure measured in the process
Delete memory:
u
Select [Lo.x] or [Hi.x].