10.3 Settings for consumed quantity monitoring
10.3.1 Quantity monitoring by pulse signal OUT1 or OUT2
►
Select [SELx] and set FLOW�
►
Select [oux] and adjust the pulse output: ImP
►
Select [ImPSx] and set pulse value (= volumetric flow quantity at which
a pulse is provided):
1� Press [
▲
] or [
▼
] to select the setting range�
2� Briefly press [
●
] to confirm the setting range�
3� Press [
▲
] or [
▼
] to set the requested numeric value�
4� Briefly press [
●
] to apply the value�
►
Select [ImPRx] and set YES�
Menu OUTx:
[SELx]
[oux]
[ImPSx]
[ImPRx]
10.3.2 Quantity monitoring by preset counter OUT1 or OUT2
►
Select [SELx] and set FLOW�
►
Select [oux] and adjust the pulse output: ImP
►
Select [ImPSx] and set the volumetric flow quantity at which output x
switches�
►
Select [ImPRx] and set NO�
Menu OUTx:
[SELx]
[oux]
[ImPSx]
[ImPRx]
10.3.3 Manual counter reset
►
Select [rTo] and set rES�T�
> The totaliser is reset to zero�
Menu EF:
[rTo]
10.3.4 Time-controlled counter reset
►
Select [rTo] and set the requested value (intervals of hours, days or
weeks)�
> The totaliser is reset automatically with the value now set�
Menu EF:
[rTo]
10.3.5 Deactivation of the counter reset
►
Select [rTo] and set OFF�
> The totaliser is only reset after overflow�
Menu EF:
[rTo]