26
Explanations submenu OUT1
Parameter
Explanation and setting options
SEL1
standard unit of measurement for evaluation by OUT1:
FLOW (volumetric flow) or TEMP (temperature) or PRES (pressure)
ou1
output function for OUT1:
• flow Hno, Hnc, Fno, Fnc, ImP
• temperature: Hno, Hnc, Fno, Fnc
• pressure: Hno, Hnc, Fno, Fnc
Hno = switching signal with hysteresis function normally open
Hnc = switching signal with hysteresis function normally closed
Fno = switching signal with window function normally open
Fnc = switching signal with window function normally closed
ImP = consumed quantity monitoring (totaliser function)
OFF = output OFF (of high impedance)
SP1
set point for OUT1
rP1
reset point for OUT1
FH1
upper limit value for OUT1
FL1
lower limit for OUT1
ImPS1
pulse value = volumetric flow quantity at which 1 pulse is delivered�
ImPR1
configuration of OUT1 for consumed quantity monitoring:
YES (pulse signal), no (switching signal)�
dS1
switching delay on OUT1
dr1
switch-off delay on OUT1
FOU1
response of OUT1 / OUT2 in case of an internal fault:
OU = output reacts as in normal case
On = output switches ON / analogue signal goes to 21�5 mA�
OFF = output switches OFF / analogue signal goes to 3�5 mA�
FOU1 is not available if ou1 = ImP was selected�