12 Troubleshooting

The unit has many self-diagnostic options. It monitors itself automatically during operation.

Warnings and error states are displayed even if the display is switched off. Error indications are also
available via IO-Link.

The status signals are classified according to NAMUR recommendation NE107.

If several diagnostic events occur simultaneously, only the diagnostic message of the event with the
highest priority is displayed.

If the measured temperature value fails, the process value for flow rate is still available.

Additional diagnostic functions are available via IO-Link 

Ò

 IO-Link interface description at

documentation.ifm.com

.

12.1 Error messages

Indication

Problem/remedy

Display off

Supply voltage too low.

u

Check the supply voltage.

Display switched off.

u

Check whether [diS] = OFF is set and change setting if necessary.

Err

Unit faulty / malfunction.

u

Replace the unit.

Measured value outside the detection zone.

• Flow value > 130% of the final value of the measuring range.

• Temperature value < -43 °C (< -46 °F) or > 133 °C (> 272 °F)

u

Check volumetric flow range / temperature range.

IOE.n

Malfunctioning. The unit is defective.

u

Replace the unit.

SC1

Switching status LED for OUT1 flashing: short circuit OUT1.

u

Check switching output OU1 for short circuit or excessive current.

SC2

Switching status LED for OUT2 flashing: short circuit OUT2.

u

Check switching output OUT2 for short circuit or excessive current.

SC

Switching status LEDs for OUT1 and OUT2 flashing: short circuit OUT1 and OUT2.

u

Check switching outputs OUT1 and OUT2 for short circuit or excessive current.

Loc

Setting keys on the unit locked, parameter change rejected.

u

Unlock the unit using the unit keys.

C.Loc

Setting buttons on the unit temporarily locked, parameter setting via IO-Link communication ac-
tive.

u

Finish parameter setting via IO-Link communication.

S.Loc

Setting keys locked via parameter setting software, parameter change rejected.

u

Unlock the unit via IO-Link interface using the parameter setting software.

PARA

Parameter setting outside the valid range.

u

Check parameter setting.

OL

Display range of volumetric flow or temperature exceeded:

• flow value between 120...130 % of the final value of the measuring range.

• temperature value between 122...133 °C (252...272 °F).

u

Check volumetric flow range / temperature range.

UL

Value below the minimum value of temperature display range:

• temperature value between -32...-43 °C (-26...-46 °F).

u

Check the temperature range.

Summary of Contents for SB03 Series

Page 1: ...Operating instructions Mechatronic flow sensor SB1xxx SB2xxx SB3xxx SB4xxx SB5xxx SB6xxx SB7xxx SB8xxx SB9xxx SB03xx 11374547 00 01 2022 GB...

Page 2: ...the unit keys 15 10 2 Parameter setting via IO Link 15 10 3 Output functions 16 10 3 1 Switching signal 16 10 3 2 Analogue signal 17 10 3 3 Frequency signal 19 10 3 4 Error behaviour of the outputs 21...

Page 3: ...QR code on the unit packaging or at www ifm com 1 1 Symbols used Requirement Instructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may r...

Page 4: ...by the architect of the system Read this document before setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environme...

Page 5: ...nded use The unit monitors industrial oils The unit detects the process categories volume flow volumetric flow quantity time and medium temperature ATTENTION Frost formation of the medium w The sensor...

Page 6: ...w Analogue signal temperature 4 3 IO Link IO Link is a communication system for connecting intelligent sensors and actuators to automation systems IO Link is standardised in the IEC 61131 9 standard G...

Page 7: ...n u Avoid major changes of cross section on the inlet side Use max one connection size smaller u Fit the unit in the pipe in accordance with the flow direction arrow and tighten at the spanner flats D...

Page 8: ...e M8 depth 6 mm on the bottom side of the unit Information about available accessories at www ifm com 5 4 Installation in case of medium containing dirt u Use a 200 micron filter in front of the inlet...

Page 9: ...2 L 4 3 2 1 Fig 4 Wiring diagram colours to DIN EN 60947 5 2 BK black BN brown BU blue WH white Pin Assignment 1 L 3 L 4 OUT1 Switching signal flow Switching signal temperature Frequency signal flow F...

Page 10: ...Operating and display elements 1 3 4 2 5 Fig 6 Operating and display elements 1 Switching status LED for OUT1 2 Switching status LED for OUT2 3 Process value in the indicated unit of measurement 4 4...

Page 11: ...re also available via the IO Link interface Process value display Main menu Extended functions EF Basic settings CFG Min max memory MEM Display settings DIS Fig 7 Menu overview 8 1 Main menu and subme...

Page 12: ...MEM DIS Main menu Fig 9 Extended functions EF menu ou2 Hno Hnc Fno Fnc I P n dAP dAA SEL1 SEL2 EF CFG FLOW TEMP FLOW TEMP nPn PnP 0 1 0 ou1 Hno Hnc Fno Fnc FRQ uni F m3h Lmin GPH GPm uni T C F CGA 100...

Page 13: ...r FrPx is output FHx Upper limit for switching signal OUTx with window function FLx Lower limit for switching signal OUTx with window function FOUx Behaviour of output OUTx in case of an error FrPx Fr...

Page 14: ...unit is in the normal operating mode It carries out its measurement and evaluation functions and generates output signals according to the set parameters During the power on delay time the outputs ar...

Page 15: ...o not touch the device with your hands u Use another object e g a ballpoint pen to carry out settings on the unit Parameter setting process in general Intent Action Change from the process value displ...

Page 16: ...e rP value must be lower than the SP value The distance between SP and rP is at least 0 6 of the final value of the measuring range hysteresis If only the set point is changed the reset point is chang...

Page 17: ...teresis function u Call up Parameters Output Configuration u Select oux and set the switching signal Hno or Hnc u Call up Parameters Digital Output x u Call up flow or temperature u Select SP_FHx_FLOW...

Page 18: ...temperature 1 Analogue signal MAW Initial value of the measuring range 2 Temperature MEW Final value of the measuring range 3 Measuring range OL Above the display range 4 Display range UL Below the di...

Page 19: ...x and FEPx 6 5 of the final value of the measuring range flow rate measurement 20 of the final value of the measuring range temperature measurement If the measured value is outside the measuring range...

Page 20: ...FRQ u Call up the main menu u Select FSP1 and set the lower measured value at which 0 Hz is output FSP1 is only available for temperature measurement u Select FEP1 and set the upper measured value at...

Page 21: ...ured value 10 3 4 1 Parameter setting via unit keys Error behaviour of the outputs u Call up the menu EF CFG u Select FOUx and set the error behaviour for OUTx On OFF OU 10 3 4 2 Parameter setting via...

Page 22: ...luences the slope of the measurement characteristic of the flow measurement The sensor is suitable for oils with indicated viscosity Technical data at documentation ifm com The indicated viscosity app...

Page 23: ...g 10 4 4 1 Parameter setting via unit keys Output polarity u Call up the menu EF CFG u Select P n and set PnP or nPn 10 4 4 2 Parameter setting via IO Link Output polarity u Call up Parameters Output...

Page 24: ...T Minimum value memory for temperature Hi T Maximum value memory for temperature It makes sense to delete the memories as soon as the unit operates under normal operating conditions for the first tim...

Page 25: ...rd process value 10 5 1 2 Parameter setting via IO Link Display standard process value u Call up Parameters Display Setting u Select SELd Displayed measurement and set the standard process value 10 5...

Page 26: ...s in the process value display 10 5 3 Display update rate The refresh rate of the display can be set via the parameter diS Selectable values d1 fast every 50 ms d2 medium every 200 ms d3 slow every 60...

Page 27: ...ess value display can be permanently switched off in the operating mode Pressing a key switches the display on In case of inactivity the display switches off again after a few seconds The LEDs remain...

Page 28: ...nit of measurement and other views w After 30 s the unit returns to the standard display 1 2 Fig 22 Process value display 1 Standard display as set under SELd and uni Example SELd FLOW and uni m3 h 2...

Page 29: ...e temperature range IOE n Malfunctioning The unit is defective u Replace the unit SC1 Switching status LED for OUT1 flashing short circuit OUT1 u Check switching output OU1 for short circuit or excess...

Page 30: ...icient filtration cleaning may be required u Unscrew sensor head u Remove float and spring u Clean the inside of the float spring and housing e g by means of compressed air u Before re assembly check...