30
11.1 Parameter setting in general
Intention
Action
Change from the process value display to the main menu
[●]
Change to the submenu
Use [▼] to navigate to
the submenu (e.g.
EF), then [●]
Select the requested parameter
[▲] or [▼]
Change to the setting mode
[●]
Modification of the parameter value
[▲] or [▼] > 1 s
Apply the set parameter
[●]
Exit parameter setting without saving
[▲] and [▼]
Return to the next higher menu level
(repeat several times to reach process value display)
[▲] and [▼]
Return to the process value display
> 30 seconds
(timeout)
11.2 Presetting
Before setting the parameters, first check the following default settings and
change them if necessary:
- [SEL2]: Process value for OUT2
- [ModE]: Operating mode
- [uni]: Standard unit of measurement for flow
11.2.1 Process value for OUT2
u
Select the CFG menu.
u
Select [SEL2]. Select process value for output 2:
• TEMP: temperature
• FLOW: flow
11.2.2 Operating mode
u
Select the INI menu.
u
Select [ModE] and define the operating mode: REL or GAS.