9.2 Setting of the output signals
9.2.1 Setting of the unit of measurement for system pressure
►
Select [Uni] and set the unit of measurement:
[bAr], [mbar], [MPa], [kPa], [PSI]�
9.2.2 Setting of the output function
►
Select [OU1] and set the function:
-[Hno] = hysteresis function / normally open
-[Hnc] = hysteresis function / normally closed,
-[Fno] = window function / normally open,
-[Fnc] = window function / normally closed�
►
Select [OU2] and set the function:
-[Hno] = hysteresis function / normally open,
-[Hnc] = hysteresis function / normally closed,
-[Fno] = window function / normally open,
-[Fnc] = window function / normally closed,
-[dESI] = output 2 is used as a diagnostic output�
9.2.3 Setting of the switching limits
►
Select [SP1] / [SP2] and set the value at which the output switches�
►
Select [rP1] / [rP2] and set the value at which the output switches off�
rPx is always smaller than SPx� The unit only accepts values which are
lower than the value for SPx�
9.3 User settings (optional)
9.3.1 Setting of a time delay for the switching signals
[dS1] / [dS2] = switch-on delay for OUT1 / OUT2�
[dr1] / [dr2] = switch-off delay for OUT1 / OUT2�
►
Select [dS1], [dS2], [dr1] or [dr2] and set a value between 0�1 and 50 s
(at 0�0 the delay time is not active)�