23
UK
9.5.5 Set colour change of the display
►
Select [coLr] and set the function:
-[rEd] = display colour red (independent of the measured value)�
-[GrEn] = display colour green (independent of the measured
value)�
-[r1ou] = display colour red when OUT1 switches�
-[G1ou] = display colour green when OUT1 switches�
-[r2ou] = display colour red when OUT2 switches�
-[G2ou] = display colour green when OUT2 switches�
-[r-12] = display colour red when the measured value is between
the limit values of OUT1 and OUT2�
-[G-12] = display colour green when the measured value is
between the limit values of OUT1 and OUT2�
-[r-cF] = display colour red when the measured value is between
the freely definable limits [cFL]
*)
and [cFH]
*)
�
-[G-cF] = display colour green when the measured value is
between the freely definable limits [cFL]
*)
and [cFH]
*)
�
*
)
The parameters [cFL] and [cFH] can only be selected in the menu tree if
[r-cF] or [G-cF] has been activated�
►
Select [cFL] and set the lower limit
(only possible if [r-cF] or [G-cF] has been activated)�
> The setting range corresponds to the measuring range and its maximum
limit is [cFH]�
►
Select [cFH] and set the upper limit
(only possible if [r-cF] or [G-cF] has been activated)�
> The setting range corresponds to the measuring range and its minimum
limit is [cFL]�