10.2 Self-diagnostics / fault indications
The unit has many self-diagnostic options�
• It monitors itself automatically during operation�
• Warnings and faults are displayed (even if the display is deactivated), in
addition they are available via IO-Link�
Display
Status LED
OUT1
Type of fault *
)
Fault / warning
Corrective measures
none
F Supply voltage too low�
►
Check / correct the supply
voltage�
SC1
flashing
flashing F Excessive current at
switching output OUT1 **
)
�
►
Check switching output ou1 for
short-circuit or excessive current;
Remove the fault�
Loc
W Parameter setting locked via
pushbuttons�
►
→"Lock /
unlock"�
C�Loc
W Parameter setting locked
via pushbuttons, parameter
setting is enabled via IO-
Link communication
�
►
Wait until parameter setting via
IO-Link is finished�
S�Loc
W Setting buttons locked
via parameter software�
Parameter change is
rejected
�
►
Unlocking only possible via IO-
Link interface / parameter setting
software�
OL
W Process value too high
(measuring range
exceeded)�
►
Check / reduce system pressure
/ select unit with corresponding
measuring range�
UL
W Process value too low
(value below measuring
range)�
►
Check / increase system
pressure / select unit with
corresponding measuring range�
Err
flashing
F Internal fault / malfunction�
►
Contact the manufacturer�
*
)
F = fault
W = warning
**
)
The output remains deactivated as long as the excessive current / short circuit
continues�