19
UK
►
Select [rP1] and set the value at which the output is reset�
rP1 is always lower than SP1� The unit only accepts values which are lower
than SP1�
9.4.3 Set switching limits for the window function
►
[ou1] must be set as [Fno] or [Fnc]�
►
Select [FH1] and set the upper limit�
►
Select [FL1] and set the lower limit�
FL1 is always lower than FH1� The device only accepts values that are
lower than the value for [FH1]�
9.5 User settings (optional)
9.5.1 Defining the delay time for the switching output
[dS1] = on delay for OUT1�
[dr1] = off delay for OUT1�
►
Select [dS1] or [dr1] and set a value between 0 and 50 s (at 0, the delay
time is not active)�
A
B
Output function:
A:
B:
[Hno] / [Hnc]
dS
dr
FH
FL
A B
C D
Output function:
A:
B:
C:
D:
[Fno] / [Fnc]
dS
dr
dS
dr
P = system pressure; SP = set point; rP = reset point; HY = hysteresis;