8.2 Explanation of the menu
8.2.1 Explanation of menu level 1
SP1/rP1 Upper / lower limit value for system pressure at which OUT1 switches with
hysteresis setting� SP1/rP1 is displayed if the parameter [Hno] or [Hnc] was set
for OUT1 in the menu Extended Functions "EF"�
FH1/FL1 Upper / lower limit for system pressure at which OUT1 switches with window
setting� FH1/FL1 is displayed if the parameter [Fno] or [Fnc] was set for OUT1
in the menu Extended Functions "EF"�
EF
Extended functions / opening of menu level 2�
8.2.2 Explanation of menu level 2
rES
Restore factory setting�
ou1
Output function for OUT1:
• Switching signal for the pressure limits: hysteresis function [H ��] or window
function [F ��], either normally open [� no] or normally closed [� nc]�
• Output off [OFF] (function is only available in operating mode [3])�
ou2
Output function for OUT2:
• Analogue signal for the current system pressure: 4…20 mA [I] or 0…10 V [U]
• Output off [OFF] (function is only available in operating mode [3])�
dS1
Switch-on delay for OUT1�
dr1
Switch-off delay for OUT1�
uni
Standard unit of measurement for system pressure (display):
[bAr] / [mbar] / [MPA] / [kPA] / [PSI] / [inHG]�
The selectable units of measurement depend on the respective unit�
See table with setting ranges
�
Lo
Minimum value memory for system pressure�
Hi
Maximum value memory for system pressure�
dAP
Damping of the switch point / process data flow (IO-Link communication) and
the display�
dAA
Damping of the analogue output�
coLr
Assignment of the display colours "red" and "green" within the measuring range�
cFH / cFL
Upper / lower value for colour change�
Parameter only active after selection of a freely definable colour window in the
coLr parameter: [r-cF] or [G-cF]�
diS
Update rate and orientation of the display�
CMPT
Selection of the operating mode