12
9.2 Configuration of the display (optional)
►
Select [Uni] and set the unit of measurement:
[bAr], [MPA], [PSI], [inHg],
for PN007A and PN009A in addition [inHg]
►
Select [diS] and set the update rate and orientation of the display:
-[d1]: update of the measured values every 50 ms
-[d2]: update of the measured values every 200 ms
-[d3]: update of the measured values every 600 ms
-[rd1], [rd2], [rd3]: display as for d1, d2, d3; rotated by 180°
-[OFF]: the display is switched off in the operating mode
9.3 Configuration of output 1
9.3.1 Setting of the output function
►
Select [OU1] and set the function:
-[Hno] = hysteresis function / normally open,
-[Hnc] = hysteresis function / normally closed,
-[Fno] = window function / normally open,
-[Fnc] = window function / normally closed
9.3.2 Setting of the switching limits
►
Select [SP1] and set the value at which the output switches
►
Select [rP1] and set the measured value at which the output switches off
rP1 is always smaller than SP1 The unit only accepts values which are
lower than SP1
9.4 Configuration of output 2
►
Select [OU2 ] and set the analogue function:
-[I] = current signal proportional to the pressure 4…20 mA,
-[U] = voltage signal proportional to the pressure 010 V