•  Read this document before setting up the product and keep it during the entire 

service life.

•  The product must be suitable for the corresponding applications and environ-

mental conditions without any restrictions.

• 

Only use the product for its intended purpose (→ Functions and features).

• 

Only use the product for permissible media (→ Technical data). 

•  If the operating instructions or the technical data are not adhered to, personal 

injury and/or damage to property may occur. 

•  The manufacturer assumes no liability or warranty for any consequences 

caused by tampering with the product or incorrect use by the operator.

•  Installation, electrical connection, set-up, programming, configuration, operati-

on and maintenance of the product must be carried out by personnel qualified 

and authorised for the respective activity.

•  Protect units and cables against damage.

3  Function and features

The pressure monitor detects the system pressure and generates 1 output signal. 

•  In case of increasing pressure the output closes when the Set1 value is rea-

ched.

•  In case of decreasing pressure the output opens when the value „Set1 minus 

hysteresis“ is reached.

The hysteresis is fixed (2% of value of measuring range).

Applications

Type of pressure: relative pressure

Order no.

Measuring range

Permissible 

overload pressure

Bursting

pressure

bar

PSI

bar

PSI

bar

PSI

PK5520

0...400

0...5 800

600

8 700

1 600

23 200

PK5521

0...250

0...3 625

400

5 800

1 000

14 500

PK5522

0...100

0...1 450

200

2 900

1 000

14 500

PK5523

0...25

0...363

60

870

500

7 253

PK5524

0...10

0...145

25

362

300

4 350

Summary of Contents for PK55 Series

Page 1: ...Operating Instructions Electronic pressure monitor PK55xx 704522 00 03 2020 UK ...

Page 2: ...he system The system manufacturer undertakes to perform a risk assessment and to create documentation in accordance with legal and normative requirements to be provided to the operator and user of the system This documentation must contain all necessary information and safety instructions for the operator the user and if applicable for any service personnel authorised by the manufac turer of the s...

Page 3: ...configuration operati on and maintenance of the product must be carried out by personnel qualified and authorised for the respective activity Protect units and cables against damage 3 Function and features The pressure monitor detects the system pressure and generates 1 output signal In case of increasing pressure the output closes when the Set1 value is rea ched In case of decreasing pressure the...

Page 4: ...ngs there is a risk of overvoltage pulses from external sources We recommend to use the unit in protected operating environments and to limit overvoltage pulses to max 500 V 4 Installation Before mounting and removing the sensor make sure that no pressure is applied to the system 5 Electrical connection The unit must be connected by a suitably qualified electrician Voltage supply to EN50178 SELV P...

Page 5: ...ED supply voltage O K 4 process connection G A tightening torque 25 Nm 5 setting marks 6 yellow LED Set1 value reached output ON 7 sealing FPM DIN 3869 14 8 internal thread M5 To obtain the setting accuracy Set the ring to the minimum value then set the requested value More information at www ifm com ...

Reviews: