PDM360NG (CR1080, CR1081, CR9042) Target V01
2011-07-28
Configurations
Programming interfaces
51
Set CoDeSys communication parameters for the Ethernet interface
3075
►
In CoDeSys click on [Online] > [Communication Parameters...].
►
Click on [New...]
►
The window "Communication Parameters: New Channel" appears.
►
Enter a self-explanatory name, e.g. "PDM_TCP/IP".
►
Select the entry "Tcp/Ip (Level 2 Route)" (
screenshot):
►
Adopt new parameters with [OK].
►
Enter the following communication parameters for the new channel (
screenshot below):
- [Address] = e.g. 192.168.82.247 (enter here the actual IP address of the device)
- [Motorola byteorder] = yes (for all PDMs except for CR107n)
- [Motorola byteorder] = no (for all
ecomat
mobile
controllers and CR107n devices)
(Double-click to change the value step by step)
►
Adopt communication parameters with [OK].
> CoDeSys and the device should now be able to communicate via the Ethernet interface.