PDM360NG (CR1080, CR1081, CR9042) Target V01
2011-07-28
CAN in the PDM360
CAN POUs to CANopen
277
CANOPEN_ENABLE
7785
Unit type = function block (FB)
Contained in the library:
ifm_CANopen_NT_Vxxyyzz.LIB
Available for the following devices:
- BasicController: CR040n
- BasicDisplay: CR0451
- PDM360NG: CR108n, CR9042
Symbol in CoDeSys:
Description
7787
CANOPEN_ENABLE allows to switch the CANopen master on or off.
NOTE
To avoid guarding or heartbeat errors the nodes must be "shut down" via an appropriate sequence first.
If the master is restarted after a stop, all other connected nodes also have to be re-initialised.
Without CANOPEN_ENABLE, the CANopen master is started automatically, as far as this has been
selected in the configuration.
The configured baud rate is only adopted if CAN_ENABLE (
→
page
) has not been activated
before.
Parameters of the inputs
7788
Parameter
Data type
Description
ENABLE BOOL
FALSE
TRUE (edge):
The CANopen master starts according to the configuration settings.
TRUE:
The CANopen master is active.
FALSE:
The CANopen master is terminated or does not start
automatically, even if "Automatic start" is selected in the configuration
data.
CHANNEL
BYTE
CAN interface (1...n) depending on the device
Baud rate
(optional use of the parameter)
WORD
Baud rate [kbits/s]
permissible values = 20, 50, 100, 125, 250, 500, 800, 1 000
Preset = 0
Use setting from the PLC configuration