OGD25x OGD55x
Photoelectric distance sensor
28
w
The current measured value is displayed. The measured value depends on the current situation.
u
Confirm by clicking on [●].
w
The new measured value flashes once.
w
The taught value is stored in [SPx].
The sensor is aligned to the object. The set point and the reset point are set independently.
11.2.3.2 Teaching via IO-Link
u
Call up [Parameter] > [Output configuration].
u
Select the output function [Hno] or [Hnc] under [OU1] / [OU2].
u
Select the measured parameter under [SEL1] / [SEL2].
u
Call up [Parameter] > [Digital output 1 ] / [Digital output 2].
u
Select [Distance] / [Reflectivity].
u
Click on [Teach SP1] / [Teach SP2].
w
The taught value is stored in [SPx].
11.2.4 Teach – switch point for window function
The device offers the possibility to teach in a window via the teach function. For this purpose, the
window to be taught in must be in the sensor’s detection range. When the teach-in process is
completed, the currently measured values are stored in [nSPx] / [FSPx] for distance or [bSPx] / [dSPx]
for reflectivity.
If an attempt is made to teach in a window switch point that contradicts the other window switch point
of the same output, a corresponding error message is shown instead of the current measured value.
11.2.4.1 Teaching via the device keys
u
Change to menu level 1.
u
Select [OU1] / [OU2].
u
Confirm by clicking on [●].
w
Set parameter value is displayed.
u
Keep [▲] or [▼] pressed for at least 3 s.
u
Use [▲/▼] to select the output configuration [Fno] or [Fnc].
u
Confirm by clicking on [●].
u
Select [SEL1] / [SEL2].
u
Confirm by clicking on [●].
u
Keep [▲] or [▼] pressed for at least 3 s.
u
Use [▲/▼] to select the measured parameter [diSt] (distance) / [rEFL] (reflectivity).
u
Confirm by clicking on [●].
u
Select [tnx] for distance or [tbx] for reflectivity.
w
The parameter value for [nSPx] or [bSPx] is displayed.
u
Keep [▲] or [▼] pressed for at least 3 s.
w
The current measured value is displayed. The measured value depends on the current situation.
u
Confirm by clicking on [●].
w
The new measured value flashes once.