11
UK
Timeout
If no button is pressed for 15 min during the setting procedure, the unit
changes to the normal operating mode�
6.5 Electronic lock
The unit can be locked electronically to prevent unauthorised setting� On delivery
the unit is not locked�
Locking / unlocking
►
Press [OUT on] and [OUT off] simultaneously for 10 s�
> Acknowledgement is indicated by a change of the status
of the yellow LED�
> The unit is locked�
►
To unlock repeat this step�
7 Operation
7.1 Set-up
►
After installation, electrical connection and parameter setting, check whether
the unit operates correctly�
> Display by LEDs�
The red LED lights and the output FC "function check output" is switched
in case of a detection problem (insufficient object recognition, maladjust-
ment, soiling of the lens)�
After rectification of the fault and several successful switching operations,
the function check output is automatically switched off�