9  Operation

 

Check whether the unit operates correctly�

 

> The LED lights when the switching output is switched�

 

> The detected distance value is shown in the display�

9.1  Electronic lock

The unit can be locked electronically to prevent unauthorised setting� On delivery 

the unit is not locked�

Locking

 

Make sure that the unit is in the normal operating mode�

 

Keep [+]

 + 

[-]

 pressed until 

[Loc]

 is displayed�

 

> The unit is locked�

Unlocking 

 

Keep [+]

 + 

[-]

 pressed until 

[uLo]

 is displayed�

 

> The unit is unlocked�

9.2  Fault indications

Display

Possible cause

Switching output

[Hno]

[Hnc]

[++]

Too much light,  

e�g� reflective surfaces

ON

OFF

[--]

Not enough light, no object

OFF

ON

[nEA]

Object to be measured outside the 

measuring range < 30 mm

ON

OFF

[FAr]

Object to be measured outside the 

measuring range > 2500 mm

OFF

ON

[ERP]

Plausibility (e.g. object too fast)

unchanged

unchanged

[SC]

Short circuit at the switching output

Summary of Contents for O5D15 Series

Page 1: ...Operating instructions Optical distance sensor O5D15x UK 80284257 00 04 2019...

Page 2: ...ation conditions 5 5 Operating and display elements 5 6 Electrical connection 6 7 Settings 7 7 1 The sensor is to switch when the object is detected 7 8 IO Link 7 8 1 General information 7 8 2 Device...

Page 3: ...the operator the user and if applicable for any service personnel authorised by the manufacturer of the system Read this document before setting up the product and keep it during the entire service l...

Page 4: ...une 2007 Position of the product label Warning sign LASER KLASSE 1 CLASS 1 LASER PRODUCT APPAREIL A LASER CLASSE 1 3 Functions and features The unit is used as an optical distance sensor 3 1 Applicati...

Page 5: ...et switch point and a distance of 20 m from the sensor is suppressed Reflecting surfaces in the direct beam path of the sensor also in the range 20 m are to be avoided by the customer Otherwise the me...

Page 6: ...allation of electrical equipment must be adhered to Ensure voltage supply to EN 50178 Disconnect power Connect the unit as follows DC PNP 4 3 2 1 4 OUT1 normally open IO Link 2 OUT2 normally closed DC...

Page 7: ...ule IO Link master for operation The IO Link interface enables direct access to the sensor values and parameters and provides the possibility to set the parameters of the unit during operation In addi...

Page 8: ...normal operating mode Keep pressed until Loc is displayed The unit is locked Unlocking Keep pressed until uLo is displayed The unit is unlocked 9 2 Fault indications Display Possible cause Switching o...

Page 9: ...of the sensor free from soiling For cleaning do not use any solvents or cleaning agents which could damage the plastic material Do not open the module housing There are no user serviceable components...

Reviews: