MK59xx
Cylinder sensor with IO-Link
24
u
Select [SSC-EnhCtr. SSC1.2] and read the current value for counter SCT1.2.
9.8.2.3 Reset counters
Reset both counters:
u
Select [Parameters] > [Counter configuration].
u
Execute command: [Reset counter to zero].
w
Both switching cycles counters are set to 0.
Reset counters individually:
u
Select [Parameters] > [Counter configuration].
u
Execute command: [Reset SCT1.x counter].
w
The switching cycles counter SCT1.x is set to 0.
9.8.3 Magnetic field monitoring
When using the diagnostic output, the sensor can output a switching signal as soon as the magnetic
field strength is outside the valid range.
u
Read the current magnetic field strength: [Parameter] > [Signal].
9.8.3.1 Configuring magnetic field monitoring
u
Call up [Parameters] > [Output Configuration].
u
Select [oux] and set the diagnostic function for output OUTx: [dOU / diagnostic output].
u
[dFUx] and set the trigger for the switching signal: [NoData / No data]
9.8.4 Operating hours counter
The operating hours since the first set-up are stored by the unit.
The operating hours counter is stored retentively every hour. If the operating voltage is interrupted, the
time since the last full hour will be lost.
The maximum counter reading of 2,000,000 h will be retained when it has been reached (no overflow).
The current value can be read via the IO-Link interface.
u
Select [Diagnosis].
u
Select [Operating hours] and read value.
9.8.5 Power cycles
The device stores the switch-on operations since the first set-up.
The maximum counter reading of 2,000,000 will be retained when it has been reached (no overflow).
u
Select [Diagnosis].
u
Select [Power cycles] and read value.
9.8.6 Internal temperature
The sensor measures the internal temperature.