33
UK
12.3 Read / reset extreme value memory temperature
►
Select parameter [Lo.T] or [Hi.T]
►
Briefly press [Set] for reading.
> Device displays the stored maximum or minimum value for 30 s.
►
To delete the memory keep [Set] pressed until [----] is displayed.
►
Briefly press [Mode/Enter].
12.4 Fast selection level / temperature
In the operating mode:
►
Briefly press [Set].
> Display of the other process value for 30 s; the respective LED is lit.
12.5 Error indications
Possible cause
Recommended measures
[Err]
Fault in the electronics.
►
Replace the unit.
[SEnS]
• Interfering sources (e.g. EMC)
• Poor cables
• Problems with the supply voltage
►
Check electrical connection.
►
Check the connection between the
sensor and the tank ground.
[FAIL]
Error during adjustment of the
overflow prevention OP:
• Overflow prevention covered by the
medium during adjustment.
• Overflow prevention soiled.
• Minimum distances too short.
• Mounting element detected below
the overflow prevention.
• Measured value not constant.
►
Lower the level, if necessary.
►
Clean the probe.
►
Observe the notes on installation.
►
Correct the position of the overflow
prevention OP.
►
Repeat the adjustment.
►
.
[cr.UL]
Error: temperature is below approx.
-40 °C / -45 °F.
►
Check process temperature and
correct, if necessary.
[cr.OL]
Error: temperature exceeds approx.
+125 °C / +255 °F
►
Check process temperature and
correct, if necessary.
[SCx] +
LEDs
5 - 8
Flashing: short circuit in switching
output x
►
Remove the short circuit.
[SC] +
LEDs
5 - 8
Flashing: short circuit in all switching
outputs.
►
Remove the short circuit.
[PArA]
Faulty data set.
►
Reset to factory settings [rES].