11.4 Error indications
Possible cause
Recommended measures
[E�000] Fault in the electronics�
Replace the unit�
[E�031]
Probe detached from the
unit; possibly incorrect
setting of the probe length�
• Check if the probe - especially the inner probe -
is correctly screwed to the unit�
• Check the parameter [LEnG]�
[E�033]
Measurement disturbed
by heavy foam build-up or
turbulence�
• If possible, install the unit in a different position�
• If possible, prevent or exclude foam formation
or turbulences by taking appropriate measures
(e�g� add antifoaming agents or reduce the pump
output a little)�
Measurement disturbed by
separation layers (e�g� oil
layer on water)�
Remove the oil layer by suction, stir the medium,
check the composition�
Probe or process
connection soiled�
Clean probe (space between inner probe and
coaxial pipe) and process connection; then carry
out a reset�*
Installation conditions were
not adhered to�
Observe the notes in "Installation"
�
Probe length or sensitivity
(setting to the medium)
incorrect�
reset�*
[SCx]
Flashing: Short circuit in
switching output OUTx�
Remove the short circuit�
[SC�OP]
Flashing: Short circuit in
switching output OUT-OP
(overflow prevention)�
Remove the short circuit�
[SC]
Flashing: Short circuit in at
least two switching outputs� Remove the short circuit�
[PArA]
Faulty data set
Reset to factory settings [rES]�
* Carry out a reset (power off and on again)
after rectifying the fault to reset the
error message�