5 Installation
Before installing and removing the unit: Make sure that no pressure is
applied to the system and there is no medium in the pipe� Also always
note the potential dangers related to extreme machine or medium
temperatures�
5.1 Installation location / environment
• Installation preferably in closed, metal tanks or pipes�
• The sensor must be in electrical contact with the metal process connection�
When installed in plastic tanks, there may be deterioration caused by
electromagnetic interference�
►
Check the function by an application test�
►
If disturbances occur, appropriate measures must be taken
(shielding, grounding, etc )
A correct fit and function of the unit and ingress resistance of the
connection are only ensured using ifm adapters�
For use of process connections from other manufacturers:
►
Ensure mechanical compatibility�
As a rule, ifm does not assume any responsibility for ingress resistance,
hygiene and function, in particular with non-existing compatibility and
incorrect installation�
When installed in restricted spaces (e�g� pipes, tank
corners, structures) or in agitators and other moving
objects:
►
To avoid malfunction and damage on sensor
and plant, adhere to a distance of min� 15 mm
to neighbouring objects (e�g� pipe/tank walls,
structures, other sensors) (fig� 6-1)�
Fig. 6-1
15 mm
15 mm