16 Applications
16.1 Storage tank
Level control and min / max monitoring with 4 switching outputs.
Replaces 4 float switches.
Configuration of the switching outputs 1...4
SP1
maximum value exceeded → alarm
ou1
hysteresis function, normally closed (Hnc)
SP2
upper preset value exceeded
→
finish refilling
ou2
hysteresis function, normally open (Hno)
SP3
below lower preset value
→ start refilling
ou3
hysteresis function, normally closed (Hnc)
SP4
below min. value
→ alarm
ou4
hysteresis function, normally open (Hno)
rP1...4 each slightly below SPx to suppress wave movements
t
L
SP1
SP2
1
0
OUT1
Hnc
1
0
OUT2
Hno
SP3
SP4
1
0
OUT3
Hnc
1
0
OUT4
Hno
OFS
XX.X