10.3 Set output signals
10.3.1 Set output function [oux] for OUTx
►
Select [oux] and adjust the switching function:
ou1
...
ou4
[Hno] = hysteresis function / normally open
[Hnc] = hysteresis function / normally closed
[Fno] = window function / normally open
[Fnc] = window function / normally closed
If the switching output is used as an overflow prevention, the setting [oux]
= [Hnc] (NC function) is recommended. The principle of normally closed
operation ensures that wire break or cable break is also detected.
10.3.2 Define switching limits [SPx] / [rPx] (hysteresis function)
►
Make sure that the function [Hno] or [Hnc] is set for [oux].
►
First set [SPx], then [rPx].
►
Select [SPx] and set the value at which the output is set.
SP1
...
SP4
►
Select [rPx] and set the value at which the output is reset.
rP1
...
rP4
[rPx] is always smaller than [SPx]. The unit only accepts values which are lower than the
value for [SPx]. If [SPx] is shifted, [rPx] also shifts provided that the lower end of the setting
range is not reached.
10.3.3 Define switching limits [FHx] / [FLx] (window function)
►
Make sure that the function [Fno] or [Fnc] is set for [oux].
►
First set [FHx], then [FLx].
►
Select [FHx] and set the upper limit of the acceptable range.
FH1
...
FH4
►
Select [FLx] and set the lower limit of the acceptable range.
FL1
...
FL4
[FLx] is always lower than [FHx]. The unit only accepts values which are lower than the value
for [FHx]. If [FHx] is shifted, [FLx] also shifts provided that the lower end of the setting range
is not reached.