11.2.3 Set medium [MEdI]
►
Select [MEdI] and set the corresponding sensitivity:
MEdI
[CLW�1] = Water, water-based media, coolant emulsions
[CLW�2] = Water, water-based media, coolant emulsions at temperatures
> 35 °C (installation in climatic tube)�
Restricted application area of the unit with climatic tube
[OIL�1] = Oils with an increased dielectric constant (e�g� some synthetic
oils)
[OIL�2] = Oils with a low dielectric constant (e�g� mineral oils)
►
In case of doubt, select [OIL�2] for oils�
►
Check proper function by an application test!
The settings [CLW�1] and [CLW�2] suppress deposits (e�g� metal swarf)�
The settings [OIL�1] and [OIL�2] suppress a bottom layer of higher dielectric
water or swarf which is a few cm high� If no oil layer is present (or if it is
very thin), the bottom layer is detected�
11.2.4 Set overflow prevention [OP]
►
Comply with minimum distances and installation instructions�
►
Select [OP]�
►
Define the position of the overflow prevention OP�
OP
►
Set [OP] before [SP1] or [FH1]�
>
If [OP] is reduced to a value ≤ [SP1] / [FH1] after setting [SP1] / [FH1],
[SP1] / [FH1] shifts downwards�
> If [OP] is increased, [SP1] / [FH1] also increases if [OP] and [SP1] /
[FH1] are close together (1 x step increment)�