5.5 Switching outputs
The unit has 3 physical switching outputs that can be configured differently
�
Description
Setting
Switching output only responds to events
/ faults
[FOUx] = ON or OFF
[OUx] = diagnostic output
Switching output responds to process value
and possibly existing events / faults
[FOUx] = ON or OFF
Switching output only responds to process
value
[FOUx] = OU
[OUx] = HNO, HNC, FNO or FNC
Switching output neither responds to
process value nor events / faults
[OUx] = OFF
[FOUx] = ON
[FOUx] = OFF
> switching output activated in case of events / faults
> switching output deactivated in case of events / faults
The following events / faults are taken into account
-Parameter missing
-Maintenance required - Cleaning
-Device hardware fault
-Signal fault
-Plausibility error
5.6 Diagnostic data
The unit provides diagnostic data for the assessment of the operational reliability�
Besides, root cause analysis is facilitated in case of a fault
� There are four
:
-Index of level edge
-Signal strength referred to the dynamic range
-Filling edge sharpness
-Installation quality
5.6.1 Index of level edge
Indicates the electrode at which the edge of the level was detected�