34
Step 1
Set preset value to 64h� If the resolution is set to 0�01°, 64h is equal to 1°�
If the resolution is set to 0�1°, the preset value must be set to Ah to set the
current position to 1°�
Identifier
DLC Command
Index
Sub-index Service/process data
NN = 10
Download
Byte 4
Byte 5
Byte 6
Byte 7
60A
8
22
00
26
00
64
00
00
00
Step 2
Save this configuration by writing "save" to 1010Sub01�
Identifier
DLC
Command
Index
Sub-index Service/process data
NN = 10
Download
Byte 4
Byte 5
Byte 6
Byte 7
60A
8
22
10
10
01
73
61
76
65
9.39 Object 6013h - Slope Long16 Offset
This is a read only parameter� The parameter is recalculated every time Slope
Long16 preset (6012h), Slope Long32 Preset (6112) or Preset X (2600) objects
are changed� This object does not exist for JD11xx�
Sub-index
Meaning
Data type
Default value
Access
0
Offset value
Integer 16
–
ro
9.39.1
Calculation of Slope Long16 Offset
Offset Value =
Preset Value - (Physical Value x Inversion)
[Inversion is -1 if activated; 1 if deactivated]
9.40 Object 6014h - Differential Slope Long16 Offset
This parameter adds an additional, independent offset to slope long16 if scaling of
slope long16 is enabled�
Note that the values should be within the range of the position attribute according
to the resolution already set�
Sub-index
Meaning
Data type
Default value
Access
0
Offset value
Integer 16
–
rw
Object 6013h is calculated automatically in relation to the preset value, Object
6014h is defined by the user�