47
UK
9 Programming
In all described operating modes (8.1 - 8.5) a switch-off delay for the relay outputs
on terminals C5 and C6 can be set�
9.1 Programming of the switch-off delay
►
Set the rotary switch to position F�
►
Switch the unit off and on again�
>
Yellow LED [T1] flashes quickly: The unit is in the programming mode.
►
Set the rotary switch to the desired position without delay:
Pos. F 0
1
2
3
4
5
6
7
8
9 A B C D E
[s]
0�25 0�5 1 1�5 2 2�5 3
4
5
6
7
8
9 10 0
: Programming mode
>
After 2.5 seconds the yellow LED [T1] is permanently lit
> Programming is completed, the delay is stored permanently�
When the unit is switched on again, it is ready for operation with the new delay�
►
Do not change the position of the rotary switch any more�
Protection against defeating: In case of subsequent changes the unit goes
into the safe state and the LEDs [T] and [T1] indicate an error (→ fault
diagnosis). Program it again.
On delivery the outputs are set without delay, i�e� the rotary switch is at
position E�