7 Parameter setting
The device detects whether it is connected to a hardware for parameter setting via the M12 connector
and is then ready for parameter setting.
The parameter setting can be carried out with or without a sensor connected.
If a sensor is connected, any errors that occur during the parameter setting of the converter are output
via the parameter setting software.
Example of a parameter setting via PC:
Information about suitable parameter setting software at
.
u
Connect the converter IO-Link sensor ‒ 4…20 mA with the PC via an USB interface by using an
M12 connector:
Fig. 5: Parameter setting with a PC
u
If the device is not detected, update the device catalogue for the parameter setting software via the
internet.
u
Change the parameter settings in the software.
u
Transfer the parameter settings to the device.
7.1 Adjustable parameters
Parameter
Function
Values
SEL1 / SEL2
Selection of the measured variable for evaluation by
OUT1 / OUT2.
When a process value is selected, the settings for ASP
and AEP as well as the selection options for uni.x will be
automatically adjusted.
• FLOW (flow)
• TEMP (temperature)
• PRES (pressure)
• COND (conductivity)
• LEVL (level)
• DIST (distance)
• FRQ (frequency)
• ACC (acceleration)
• SPEED (speed)
• PDV1...PDV4 (Process Data Value
1...4) *
ASP1 / ASP2
Analogue start point for OUT1 / OUT2
= measured value at which the analogue value is 4 mA.
AEP1 / AEP2
Analogue end point for OUT1 / OUT2
= measured value at which the analogue signal is 20 mA.
uni.F
(FLOW)
Unit for flow
• m
3
/h
• l/min
• gal/min
• ft
3
/h
• ft
3
/min
uni.T
(TEMP)
Unit for temperature
• °C
• °F