background image

15

UK

6  Electrical connection

The unit must be connected by a qualified electrician�

The national and international regulations for the installation of electrical 

equipment must be adhered to�

Voltage supply to EN50178, SELV, PELV�

 

► Disconnect power�

 

► Connect the unit as follows:


Pin1

Ub+

Pin3

Ub-

Pin4 

(OUT1)

Switching signal: limit values for volumetric flow�

Switching signal: quantity meter reached preset value�

Pulses: 1 pulse every time the defined volumetric flow is reached�

Pin2

(OUT2/InD)

Switching signal: limit values for volumetric flow�

Switching signal: limit values for temperature�

Analogue signal for volumetric flow�

Analogue signal for temperature�

Input for signal “meter reset”�

Core colours of ifm sockets:

1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4 = BK (black)

Summary of Contents for Efector 300 SM8100

Page 1: ...structions Magnetic inductive flow sensor SM8100 704989 00 01 2011 UK Tel 44 0 191 490 1547 Fax 44 0 191 477 5371 Email northernsales thorneandderrick co uk Website www heattracing co uk www thorneand...

Page 2: ...Start up delay dSt 10 5 Installation 11 5 1 Installation location 11 5 2 Installation in pipes 14 5 3 Protection against high medium temperatures 14 6 Electrical connection 15 7 Operating and display...

Page 3: ...of the standard display 23 9 5 3 Setting the output logic 23 9 5 4 Setting the start up delay 23 9 5 5 Setting the damping of the measured values 23 9 5 6 Setting the error behaviour of OUT1 OUT2 24...

Page 4: ...lead to malfunctions of the unit or to unwanted effects in your application That is why installation electrical con nection set up operation and maintenance of the unit must be carried out by qualifie...

Page 5: ...al for volumetric flow limit value 9 2 2 or switching signal for temperature limit value 9 4 1 or analogue signal for volumetric flow 9 2 3 or analogue signal for temperature 9 4 2 OUT2 pin 2 cannot o...

Page 6: ...n meter subtracts Counting pulses are only provided as the sum increases After subtraction consumded quantity decreases pulses are not provided again before the consumded quantity has exceeded the for...

Page 7: ...and remains switched until the meter is reset 4 4 Monitoring of temperatures A switching signal for temperature limit values can be provided on output 2 For the switching functions 4 5 An analogue si...

Page 8: ...switching state of the output stable if the volumetric flow varies slightly 4 6 Volumetric flow or temperature monitoring analogue function The analogue start point ASP determines at which measured va...

Page 9: ...between 0 and 10 V It is also indicated Volumetric flow above the measuring range output signal 10 V Current output 4 20 mA example volumetric flow monitoring Factory setting Measuring range scaled ME...

Page 10: ...re 3 options The volumetric flow quantity increases quickly and reaches the switch point good range within dSt outputs remain active The volumetric flow quantity increases slowly and does not reach th...

Page 11: ...ches again 0 5 of VMR dSt starts output becomes active 7 dSt elapsed Q has not reached good range output is reset 8 Q reaches good range output becomes active 5 Installation 5 1 Installation location...

Page 12: ...g pipe F flow direction Avoid the following installation locations Directly in front of a falling pipe In a falling pipe F flow direction At the highest point of the pipe system Directly in front of t...

Page 13: ...the pipe system The pipes are always completely filled On the suction side of a pump F flow direction If installed in an ungrounded pipe system e g plastic pipes the unit must be grounded Ground brac...

Page 14: ...hten the two adapters in opposite direction tightening torque 30 Nm After installation air bubbles in the system can affect the measurement Help Rinse the system after installation for ventilation rin...

Page 15: ...Pin1 Ub Pin3 Ub Pin4 OUT1 Switching signal limit values for volumetric flow Switching signal quantity meter reached preset value Pulses 1 pulse every time the defined volumetric flow is reached Pin2 O...

Page 16: ...Ds 4 and 6 flashing consumed quantity before the last reset in 103 cubic metres LED 5 current medium temperature in C LED 7 LED 8 switching state of the corresponding output 9 Alphanumeric display 4 d...

Page 17: ...17 UK 8 Menu 8 1 Menu structure Mode Enter Set l or m3 current meter count in l m3 or 1000 m3 l or m3 stored meter count in l m3 or 1000 m3...

Page 18: ...alue for volumetric flow or temperature AEP Analogue end value for volumetric flow or temperature DIn2 Configuration of the input pin 2 for meter reset EF Extended functions opening of menu level 2 HI...

Page 19: ...eter flashes for 5 s After 5 s The setting value is changed incremental by press ing briefly or scrolling by holding pressed Numerical values are incremented continuously If the value is to be reduce...

Page 20: ...ode Enter Set for 10 s Loc is displayed During operation Loc is briefly displayed if you try to change parameter values Press Mode Enter Set for 10 s uLoc is displayed When delivered unlocked Time out...

Page 21: ...unction normally closed Select SP2 and set the value at which the output switches Select rP2 and set the value at which the output switches back 9 2 3 Scaling of the analogue value for volumetric flow...

Page 22: ...als from 1 hour to 8 weeks Press Mode Enter briefly 9 3 4 Switch off the meter reset Select rTO and set OFF The meter is only reset after overflow factory setting 9 3 5 Settings for meter reset by an...

Page 23: ...t accuracy 9 5 2 Configuration of the standard display Select SELd and determine the standard process category FLOW display shows the current volumetric flow value in the stand ard unit of measurement...

Page 24: ...th the parameters The analogue signal corresponds to the measured value 9 6 Service functions 9 6 1 Reading the min max values for volumetric flow Select HI or LO and press Set briefly HI maximum valu...

Page 25: ...tion Set OU1 to ImP 9 3 2 Press Mode Enter until ImPS is displayed Press Set and keep it pressed The current numerical value flashes for 5 s then one of the 4 digits becomes active digit flashes can b...

Page 26: ...the right flashes becomes active 8 1 2 3 no pushbutton pressed after 3 s 8 1 2 3 after 3 s 8 1 2 3 after 3 s 8 1 2 3 If the fourth digit flashes unchanged for 3 s digit 1 becomes ac tive again if the...

Page 27: ...eter value for approx 15 s After another 15 s the parameter is displayed again then the unit returns to the Run mode 10 2 Changing the display unit in the Run mode Press Set briefly in the Run mode Pr...

Page 28: ...medium temperatures over 50 C some parts of the housing can heat up to over 65 C In this case do not touch the unit Protect the housing against contact with flammable substances and uninten tional con...

Page 29: ...ble Max load current output 500 Min load for voltage output k 2 Pulse value 0 01 l 100 000 m Pulse length s min 0 0025 max 2 Power on delay time s 5 Flow monitoring Measuring range l min m h 0 2 100 0...

Page 30: ...N IEC 68 2 27 11ms Vibration resistance g 5 DIN IEC 68 2 6 55 2000 Hz EMC IEC 1000 4 2 ESD 4 8 KV IEC 1000 4 3 HF radiated 10 V m IEC 1000 4 4 Burst 2 KV IEC 1000 4 5 Surge 0 5 1 KV IEC 1000 4 6 HF co...

Page 31: ...5 ImPS 0 1 ImPR YES OU1 Hno OU2 I SP2 FLOW 40 0 rP2 FLOW 39 5 SP2 TEMP 20 0 rP2 TEMP 19 6 ASP FLOW 0 0 AEP FLOW 100 0 ASP TEMP 20 0 AEP TEMP 80 0 DIn2 EDG FOU1 OFF FOU2 OFF dSt 0 P n PnP dAP 0 6 rTo O...

Reviews: