CR1102
14
u
Carry out the fitting according to the indications of the cable manufacturer. The permitted maximum
is 10 Nm.
u
During installation, place the M12 connector vertically so that the coupling nut will not damage the
thread.
u
Unused sockets are equipped with protective caps (included).
Tightening torque: 1.3
±0.1
Nm
u
Use 40-pole connectors with individually sealed cores to ensure protection rating IP 67.
Only connect the connector when the supply voltage is disconnected.
"Hot plugging" is not permitted.
"Hot plugging" is permitted at the USB type A connector of the connected M12 adapter.
The ingress resistance of cables that users have cut to length must be guaranteed.
u
Use twisted-pair cables for the CAN / IFM connection.
The CAN bus is internally protected against short circuit to VBB and GND.
For CAN / IFM cables ≥ 30 m, ensure appropriate protection against surge (e. g. shielded
cables).
u
For the Ethernet connection, use a minimum category 5 (Cat 5) cable.
u
Audio loudspeaker output: floating twisted-pair wiring.
u
Audio Line-In: use a screened cable.
u
For Line-in and the headphone output, use AUDIO_GND as GND reference.
u
Video: screened, shielded twisted-pair or coaxial cable with 75 ohms impedance
5.4 General wiring information