Process and dialogue module ecomatDisplay CR1058, CR1059
17
5.2 Connection accessories
You can find more information about the available accessories at: www�ifm�com
5.3 Connection technology
Observe all notes on connection technology�
►
Note the device label�
►
Use M12 connectors with gold-plated contacts�
►
The M12 connection parts in the device comply with the ingress resistance
requirements of the standard EN 61076-2-101� To adhere to the protection
rating, only cables certified to this standard must be used� The system creators
undertake to ensure ingress resistance for cables which they cut to length
themselves�
►
Carry out the fitting according to the indications of the cable manufacturer� A
maximum of 10 Nm is permitted�
►
During installation, place the M12 connector vertically so that the coupling nut
will not damage the thread�
► Unused sockets are equipped with protective caps (included). Tightening
torque: 1�3
±0,1
Nm
►
Use 40-pole connector with individually sealed cores to ensure protection rating
IP 67�
Only connect the connector when the supply voltage is disconnected� No
"hot plugging" is permitted�
"Hot plugging" is permitted at the USB type A connector of the connected
M12 adapter�
The ingress resistance of cables which the users have cut to length
themselves has to be ensured�
►
Use twisted-pair cables for the CAN/IFM connection�
The CAN bus is internally protected against short circuit to VBB and GND.
For CAN/IFM cables ≥ 30 m, ensure appropriate protection against surge
(e�
g. shielded cables).
► Use a min. category 5 (Cat 5) cable for the Ethernet connection.
►
Audio loudspeaker output: lay twisted-pair cables with floating ground
► Video: screened, shielded twisted-pair or coaxial cable with 75 ohms
impedance