IO-Link master
40
30 Substitute value behaviour
If PROFINET communication fails, all device outputs are set to the parameterised
substitute values�
Please refer to the "Status/control module -> Start-up parameters" and
"Flexible module configuration -> Start-up parameters" chapters for the precise
parameterisation of substitute values�
31 Firmware Update ProfiNet
This document describes how you can make a firmware update for AL1000�
32 Firmware update
To upload the firmware file you will need either an FTP tool or you can use the
Windows Explorer�
This document describes the firmware update using the Windows Explorer�
The default login details are as follows:
– User: admin
– Password: private
If you use the FTP tool, please follow the appropriate steps in your tool�
32.1 Access the FTP server
To access the FTP server on the device, please enter the address in the Windows
Explorer in the following manner:
ftp://user:password@ip�address
Example
Here the default login details were used� The IP address is 172�16�49�10