IO-Link master
27
Designation
Colour
Meaning
State
Description
UA
Green/red
Actuator
supply for
X05 ��� X08
Green ON
Actuator voltage present
Green, OFF
Actuator voltage not present
Red ON
Short circuit between pin 2 and pin 5
The numbering of the LEDs is as follows:
The first position specifies the byte, the second position specifies the bit�
16 ProfiNet data model
The design of the device is modular� The first slot 1�1 (slot 1 and subslot 1) always
contains the "status/control module" with 4 bytes each of input and output process
data�
In slots 1�2 to 1�9 the operating mode and the process data length for the
respective IO-Link port are parameterised�
16.1 Status/control module
Input process data
Byte
Byte 0
Byte 1
Byte 2
Byte 3
Bit
0���7
8���15
16���23
24���27
28���31
Function
Port state
(COM status)
PD VALID
state
DI state on pin
4 (C/Q)
DI state on
pin 2
Reserved
Connection
X01���X08
X01���X08
X01���X08
X01���X04
-
Pin
4
4
4
2
-
Port
1���8
1���8
1���8
1���4
-
Output process data
Bytes
Byte 0
Byte 1
Byte 2
Byte 3
Bit
0���7
8���15
16���23
24���31
Function
Port state
(COM status)
Reserved
DO state on
pin 4 (C/Q)
Reserved
Connection
X01���X08
-
X01���X08
-
Pin
4
-
4
-
Port
1���8
-
1���8
-