Troubleshooting
Boot errors – error codes B00...B11
480
16.1
Boot errors – error codes B00...B11
6020
Menu operation interrupted.
Error message superposes the menu screen.
Error message only disappears after the following actions:
1. Error removed AND
2. Error message acknowledged with the right function key.
Error message
Cause(s)
Remedy
B00 ControllerE
boot
error
After power-on of the device, an error was found
during initialisation of the individual device
components.
For further details please refer to the following
error messages.
►
Check further error messages.
B01
Master 1 initialisation
Unsuccessful initialisation of the master.
Possible causes:
Unacceptable interference on the 24 V
power supply.
Unacceptable interference on the AS-i power
supply.
Unacceptably high electrostatic charges and
electromagnetic fields in close proximity of
the device.
►
Ground the device via the rail.
►
Connect the FE terminal to the machine
ground.
►
Use a switched-mode power supply to
supply the device with power.
B02
Master 2 initialisation
B01
B03
General FAT error
An error was found in the data field of the "File
Allocation Table" FAT.
►
Check further error messages.
B04
Only one master detected
The operating system can only detect 1 master in
the device although 2 masters should be present.
Possible cause:
Hardware fault.
►
Replace the device and project again.
B05
Two masters detected
The operating system can detect 2 masters in the
device although communication with only
1 master is allowed.
Possible cause:
Hardware fault.
B04
B06
Fieldbus type not detected
During automatic detection of the integrated
fieldbus no enabled fieldbus module could be
detected.
Possible cause:
Hardware fault.
B04