176
ifm
Programming Manual
ecomatmobile
CabinetController (CR0301) Runtime System V05
2016-04-21
ifm function elements
ifm function elements for the device CR0301
>
SET_PASSWORD
266
Unit type = function block (FB)
Unit is contained in the library
ifm_CR0301_Vxxyyzz.LIB
Symbol in CODESYS:
>
Description
13038
NOTICE
Please note for CR250n, CR0301, CR0302 and CS0015:
The EEPROM memory module may be destroyed by the permanent use of this unit!
► Only carry out the unit
once
during initialisation in the first program cycle!
► Afterwards block the unit again with ENABLE = FALSE!
269
SET_PASSWORD sets a user password for the program and memory upload with the
DOWNLOADER.
If the password is activated, reading of the application program or the data memory with the software
tool DOWNLOADER is only possible if the correct password has been entered.
If an empty string (default condition) is assigned to the input PASSWORD, an upload of the application
software or of the data memory is possible at any time.
A new password can be set only after resetting the previous password.
The password is reset when loading a new application program as boot project.
>
Parameters of the inputs
270
Parameter
Data type
Description
ENABLE
BOOL
TRUE (nur 1 Zyklus lang):
use new Parameter
FALSE:
unit is not executed
PASSWORD
STRING(16)
password
If PASSWORD = "", than access is possible without enter of a
password
>