14 Error codes of the evaluation unit
Error codes are signaled with bit “Diag” within the status byte of the response data of the evaluation unit .
If more diagnostic events are available, the channel can transfer up to 4 diagnostics simultaneously . The
hardware diagnostic events, which are device relevant, are indicated by the Diag bit on all channels .
Inactive channels can only transfer hardware diagnostic events .
Example:
Command response of the evaluation unit for command “DR”
C001
F4FE9000
14.1 Error group RFID tag (F1FE)
Error group F1
Error code
Description
Tag/transponder
F1FE0200
Tag not present, tag has left the transmission window
Tag/transponder
F1FE0300
Address or command does not match the RFID tag characteristics,
memory size invalid
Tag/transponder
F1FE0400
Tag is defective, replace tag or battery
Tag/transponder
F1FE0500
Overflow of the RFID tag memory UID > 16 bytes
Tag/transponder
F1FE0900
Command not supported by the RFID tag
Tag/transponder
F1FE0A00
Access error, e .g . block locked . See ISO18000-x
Tag/transponder
F1FE0B00
General tag error which is not specified in detail
Tag/transponder
F1FE0C00
Unknown internal error
14.2 Error group evaluation unit (F4FE)
Error group F4
Error code
Description
Evaluation unit
F4FE0100
Power supply failure
Evaluation unit
F4FE0200
Hardware failure, short circuit and overload
Evaluation unit
F4FE0201
Allowed temperature exceeded
Evaluation unit
F4FE0300
read/write head does not function because time out occurred
Evaluation unit
F4FE0400
Command buffer overflow of the IO server queue
(Internal error)
Evaluation unit
F4FE0500
Data buffer overflow, memory allocation (internal error)
Evaluation unit
F4FE0600
Command is not supported in this mode (internal error)
Evaluation unit
F4FE8100
ID-Link Master inactive . i .e . after power on (internal error)
Evaluation unit
F4FE8200
Internal IO port server error (internal error)
Evaluation unit
F4FE8300
Invalid IO port parameter, e .g . channel (internal error)
Evaluation unit
F4FE8400
Vendor-specific error with the command PUT
Evaluation unit
F4FE8500
IO port server resets channel
Evaluation unit
F4FE8600
Data not available for delayed C/Q inputs or delayed UID
(Internal fault)
Evaluation unit
F4FE8700
Reconfiguration of the IO port channel not yet allowed (internal error )
Evaluation unit
F4FE8800
Parameter flag of the IO port not set (internal error )
Evaluation unit
F4FE8900
General error detected by ID-Link master
Evaluation unit
F4FE8A00
CRC error detected by ID-Link Master
Evaluation unit
F4FE8B00
Object not found detected by ID-Link Master
Evaluation unit
F4FE8C00
Data read/write area in the command not valid
Evaluation unit
F4FE8D00
IO port channel reconfigured
Evaluation unit
F4FE8E00
The read/write head could not process the command, i .e . read/write length
exceeded, tag memory error, write to locked block
Evaluation unit
F4FE8F00
Tag data length exceeded (block size * block number)
Evaluation unit
F4FE9001
Short circuit at output driver detected (C/Qo)
Evaluation unit
F4FE9002
Undervoltage at output driver detected (AUX or L+)
Evaluation unit
F4FE9003
Overload at output driver detected (L+ or C/Qo)
Evaluation unit
F4FE9004
Over temperature at output driver detected