Analogue threshold display
DP2200
23
10 Operation
After power on, the device is in the operating mode (SIO). It carries out its measurement and
evaluation functions and provides output signals according to the set parameters (
Ò
Menu).
10.1 Functions output 1
OUT1 (connector, pin 4):
•
Digital output (SIO)
•
IO-Link interface
Selectable switching functions:
•
Hysteresis functions, normally open / normally closed: SP1/rP1 ─ set point/reset point OUT1
(
•
Window functions, normally open / normally closed: FH1/FL1 ─ min/max switching limits for
window function (
OUT1 changes its status if the input signal is above or below the set switching limits. First the switch
point SP1 is set, then the reset point rP1: SP1/rP1 ─ set point/reset point OUT1 (
15).
The hysteresis defined remains even if [SP1] is changed again. Changing the parameter [rP1]
also changes the hysteresis.
The width of the window can be set by means of the difference between FH1 and FL1.
FH1 = upper value
FL1 = lower value
10.2 Functions output 2
OUT2 (connector, pin 2):
•
Analogue output (looping through the analogue input signal)